POWER DISTRIBUTION UNIT (PDU)
MODELS AND SPECIFICATIONS
Basic PDUs 1
Metered PDUs 2
Monitored PDUs 3
Switched PDUs 4
ATS PDUs 5
Hot-Swap PDUs 5
Power Cords 6
Plug and Outlet Guide 7
PDU Accessories 8
Basic PDUs
Reliable Power
Distribution
Model
Nominal
AC Voltage
(50/60 Hz)
Max
Input
Current
(A)
Meters/
Output
Banks
Nominal
Load
Capacity
(B)
Input
Plug Type
Input
Cord
Length
Outlets
(G)
(Quantity & Type) Rack Size
(H)
SINGLE-PHASE HORIZONTAL BASIC PDUs
PDU1215
100/120/127 V 15 A 0/1 1.8 kW 5-15P
15 ft. 13 (5-15R) 1U or 0U (17.5 in.)
PDU1220
100/120/127 V 20 A 0/1 2.4 kW 5-20P
15 ft. 13 (5-15/20R) 1U or 0U (17.5 in.)
PDU1220T
100/120/127 V 20 A 0/1 2.4 kW L5-20P
15 ft. 13 (5-15/20R)
1U or 0U (17.5 in.)
PDU2430
100/120/127 V 30 A 0/2 3.6 kW L5-30P
15 ft. 24 (5-15R) 1U or 0U (17.5 in.)
PDU12IEC
100 to 240 V 16 A 0/1 3.8 kW C20 inlet
(C)
N/A
(F)
14 (12 C13 + 2 C19)
1U or 0U (17.5 in.)
PDUNV
100 to 240 V 16 A 0/1 3.8 kW
6 options
(C20 inlet)
(C,D)
10 ft. 14 (12 C13 + 2 C19)
1U or 0U (17.5 in.)
PDUH20DV
100 to 240 V 20 A 0/1 4.8 kW L6-20P (C20 inlet)
(C)
12 ft. 14 (12 C13 + 2 C19)
1U or 0U (17.25 in.)
PDUH20HVL6
208/240 V 20 A 0/1 4.8 kW L6-20P
15 ft. 14 (12 C13 + 2 C19)
1U or 0U (17.25 in.)
PDU1230
208/240 V 30 A 0/8 7.2 kW L6-30P
15 ft. 20 (16 C13 + 4 C19)
1U or 0U (17.5 in.)
SINGLE-PHASE VERTICAL BASIC PDUs
PDU1415
100/120/127 V 15 A 0/1 1.8 kW 5-15P
15 ft. 14 (5-15R) 0U (24 in.)
PDUV15
100/120/127 V 15 A 0/1 1.8 kW 5-15P
15 ft. 14 (5-15R) 0U (36 in.)
PDU1420T
100/120/127 V 20 A 0/1 2.4 kW L5-20P
15 ft. 14 (5-15/20R)
0U (24 in.)
PDUV20
100/120/127 V 20 A 0/1 2.4 kW L5-20P / 5-20P
(E)
15 ft. 14 (5-15/20R) 0U (36 in.)
PDU40TDUAL
100/120/127 V 2 x 20 A 0/2 4.8 kW
2 x L5-20P / 2 x 5-20P
(E)
2 x 10 ft. 40 (5-15/20R) 0U (70 in.)
PDUV30HV
208/240 V 30 A 0/2 7.2 kW L6-30P
10 ft. 38 (32 C13 + 6 C19)
0U (63.75 in.)
Certifications vary by model. (A) Agency-derated input current is 80% of maximum. (Does not apply to 230 V applications.) (B) Load capacity varies with voltage and applicable derating.
(C) For 230 V applications, connect the inlet to a user-supplied input cord with a region-specific plug. (D) Includes fixed input cord terminating in C20, plus adapters for C14, 5-15P,
5-20P, L5-20P and L6-20P. (E) Includes twist-lock L5-20P plugs with adapters to convert to straight-blade 5-20P plugs. (F) User-supplied cord. (G) 5-15/20R outlets are compatible
with 5-15P and 5-20P plugs. (H) 1U and 2U represent horizontal rack installation. 0U represents vertical rack installation. Included brackets also support surface mounting. Select 1U
models also support vertical installation with optional PDUSIDEBRKT accessory.
FIND IT FAST!
Try our interactive PDU selector guide at www.tripplite.com/pdu-guide
POWER DISTRIBUTION UNIT (PDU)
MODELS AND SPECIFICATIONS
Updated October 2013
Kommentare zu diesen Handbüchern